Using a KNX server like eibd with PHP in combination, you might come to a point where you want to convert the DPT/EIS encoded telegram values to decimal format.
For some data types, it works by simply using PHP hexbin(), but it does not for 2-byte floating point values.
In many forum threads the following sample is used:
$first_byte = decbin(hexdec(substr($value, 0, 2)));
$second_byte = decbin(hexdec(substr($value, 2, 2)));
while (strlen($first_byte) != 8) {
$first_byte= "0".$first_byte;
}
while (strlen($second_byte) != 8) {
$second_byte= "0".$second_byte;
}
$tmpdata = $first_byte.$second_byte;
$eib_base_value=bindec(substr($tmpdata,5,15));
$eib_exponent=bindec(substr($tmpdata,1,4));
return (0.01*$eib_base_value)*pow(2,$eib_exponent);
BUT it converts negative values wrong! This can lead to e.g. wrong temperature values which might affect the heating control.
Use this snippet instead:
$intValue = hexdec($value);
$floatValue = ($intValue & 0x07ff);
if (($intValue & 0x08000) != 0)
{
$floatValue = $floatValue | 0xfffffffffffff800;
$floatValue = $floatValue *-1;
}
$floatValue = $floatValue << (($intValue & 0x07800) >> 11);
if (($intValue & 0x08000) != 0)
{
$floatValue = $floatValue * -1;
}
return $floatValue / 100;